Repair

Fault codes Viessmann

Type the code your boiler shows: what it means, what you can do, and when a technician is needed.

Sometimes a number follows the code (6A 227): type it too, the page shows what it means.

Your brand

All codes Viessmann

0A Gas pressure too low or CO alarm
0C Mains voltage too low
0E Flue gas monitor tripped
0F Boiler service due
0b Heating water flow too low
1E Flow sensor faulty
1F Flow sensor faulty
1d Flow sensor: no communication
2A Solar circuit flow and return swapped
3A LAN communication module fault
3C Network: DHCP server not responding
3E Internet transmission error
3F LAN module update failed
3b LAN module memory problem
3d Fan unit fault or network cable unplugged
4C Heating circuit 3 flow sensor open circuit
4d Circuit 3 mixing valve kit wrongly set
5A Flow sensor or buffer tank sensor broken
9A Solar collector sensor open circuit
9C Solar hot water sensor open circuit
9E Solar circuit flow too low
9F Solar controller fault
9b Open circuit on a Vitosolic controller sensor
A.11 System water pressure too low
A.12 Boiler clock battery flat
A.18 Condensate may have built up in the boiler
A.19 The monitoring thermostat has tripped
A.20 Service reminder could not be activated
A2 Water pressure too low
A3 Flue gas temperature sensor wrongly placed
A4 Water pressure too high
A6 Impressed current anode faulty
A7 Control module faulty
A8 Air in the pump or low water flow
A9 OpenTherm link lost or internal pump blocked
C1 EA1 extension or external safety device
C2 Connection to the solar controller lost
C3 Connection to the AM1 extension lost
C4 Connection to the Open Therm extension lost
C5 Variable-speed pump: communication lost
C6 Circuit 2 pump: communication lost
C7 Circuit 1 pump: communication lost
C8 Circuit 3 pump: communication lost
C9 Fault message from an external device
CE Connection to an extension module lost
CF LON communication module fault
Cd Communication fault with the Vitocom 100
E0 Fault on an external LON network device
E0-EF Fault in a heating BUS device
E1 Flame signal too high during calibration
E2 No calibration, water flow too low
E3 Safety chain fault or heat not drawn off
E4 Fault in the control's 24 V supply
E5 Internal fault or flame amplifier fault
E6 Water pressure too low
E7 Flame signal too low during calibration
E8 Flame signal outside the allowed range
E9 Flame loss or abnormal flame signal during calibration
EA Implausible flame signal during calibration
EC Error during combustion calibration
EE No flame when the burner starts
EF Flame lost right after ignition
Eb Combustion calibration interrupted
Ed Internal fault in the control
F.100 PlusBus voltage fault
F.104 External fault input activated
F.11 Solar collector temperature sensor open circuit
F.12 Solar collector temperature sensor short circuit
F.13 Outdoor temperature sensor open circuit
F.1312 Boiler time zone not set
F.14 Outdoor temperature sensor short circuit
F.142 Communication fault with the fan unit
F.15 Lower solar cylinder sensor open circuit
F.16 Lower solar cylinder sensor short circuit
F.160 CAN bus communication fault
F.161 Data memory access fault
F.162 Processor supply voltage too low
F.163 Memory checksum error in the burner control
F.180 Gas pressure too low
F.182 Outlet temperature sensor short circuit
F.183 Outlet temperature sensor open circuit
F.184 Safety temperature limiter short circuit
F.185 Safety temperature limiter open circuit
F.19 Lower hot water cylinder sensor open circuit
F.29 Low loss header sensor open circuit
F.299 Real-time clock fault
F.342 Burner control unit communication fault
F.345 Temperature monitor tripped
F.346 Ionisation current calibration error
F.348 Gas valve calibration failed
F.349 Air mass flow not detected correctly
F.350 Ionisation voltage fault
F.351 Ionisation current out of range
F.352 Internal CO limit exceeded
F.353 Insufficient gas supply, reduced burner output
F.354 Gas modulation valve out of tolerance
F.355 Abnormal flame signal at burner start
F.357 Insufficient gas supply
F.359 No ignition spark
F.361 No flame signal at burner start
F.364 Internal system fault
F.365 Gas valve relay contact faulty
F.366 Gas valve power cannot be switched off
F.367 Gas valve stays powered
F.368 Gas pressure switch fault
F.369 Flame missing or lost at burner start
F.370 Gas valve closing not confirmed
F.371 Fan speed too low
F.372 Repeated flame loss during calibration
F.373 Overheating during burner calibration
F.375 Ionisation current calibration failed
F.377 Ionisation current recalibration not possible
F.378 Flame lost during the stabilisation phase
F.379 Flame signal missing or too weak
F.380 Flame lost right after it forms
F.381 Flame lost during operation
F.382 Fault counter limit exceeded
F.383 Fuel valve does not close
F.384 Gas valve does not close
F.385 Short circuit, ionisation current signal 1
F.386 Open circuit, ionisation current signal 1
F.387 Short circuit, ionisation current signal 2
F.388 Open circuit, ionisation current signal 2
F.393 Short circuit, flue gas temperature sensor 2
F.394 Open circuit, flue gas temperature sensor 2
F.395 Short circuit, flame temperature signal 1
F.396 Open circuit, flame temperature signal 1
F.399 Short circuit, ionisation voltage signal 1
F.400 Open circuit, ionisation voltage signal 1
F.401 Short circuit, ionisation voltage signal 2
F.402 Open circuit, ionisation voltage signal 2
F.403 Short circuit, dynamic ionisation current 1
F.404 Burner control unit faulty
F.405 Short circuit, dynamic ionisation current 2
F.406 Burner control unit faulty
F.408 Fuel valve relay 1
F.410 Burner control unit faulty
F.416 Flue gas temperature sensor wrongly positioned
F.417 Short circuit on the 24 V supply
F.418 Burner control unit faulty
F.425 Time synchronisation failed
F.430 Gateway communication fault
F.431 KNX gateway communication fault
F.436 Flow rate sensor short circuit
F.437 Flow sensor open or short-circuited
F.446 Flow sensor and safety limiter disagree
F.447 Ionisation voltage signal deviation
F.448 Ionisation current signal deviation
F.449 Program sequence timing fault
F.450 Program sequence timing fault
F.451 Program sequence timing fault
F.452 Program sequence timing fault
F.453 Sequence synchronisation error
F.454 Wrong software version
F.455 Program sequence monitoring fault
F.456 Wrong system state at start-up
F.457 Boiler fan blocked
F.458 Internal fault: faulty reset sequence
F.463 Flame signal too weak during calibration
F.464 Flame signal weak and implausible during calibration
F.467 Gas supply too low during calibration
F.468 Flame signal too high during calibration
F.471 System pressure sensor not available
F.473 HMU central module communication fault
F.474 Fault in the program timing monitoring
F.477 Abnormal temperature difference in the solar circuit
F.49 Flue gas temperature sensor open circuit
F.517 Wired remote control communication fault
F.527 Parameter update not completed
F.528 Basic programming wrong or incomplete
F.530 Solar function limited: sensor values missing
F.538 System return sensor open circuit
F.539 System return sensor short-circuited
F.540 Condensate building up in the heat cell
F.544 Circuit 2 flow sensor open circuit
F.545 Circuit 2 flow sensor short-circuited
F.546 Circuit 3 flow sensor open circuit
F.547 Circuit 3 flow sensor short-circuited
F.548 Circuit 4 flow sensor open circuit
F.549 Circuit 4 flow sensor short-circuited
F.57 Room temperature sensor open circuit
F.574 Circuit 1 room sensor not available
F.575 Circuit 1 room sensor open circuit
F.576 Circuit 1 room sensor short-circuited
F.577 Circuit 2 room sensor not available
F.578 Circuit 2 room sensor open circuit
F.579 Circuit 2 room sensor short-circuited
F.580 Circuit 3 room sensor not available
F.581 Circuit 3 room sensor open circuit
F.582 Circuit 3 room sensor short-circuited
F.583 Circuit 4 room sensor not available
F.584 Circuit 4 room sensor open circuit
F.585 Circuit 4 room sensor short-circuited
F.62 Safety temperature limiter tripped
F.63 Flue gas temperature limiter tripped
F.64 Flame lost during operation
F.65 No flame when the burner starts
F.666 Hot water preheating sensor TS3 open circuit
F.667 Hot water preheating sensor TS3 short-circuited
F.668 Hot water reheating sensor TS4 open circuit
F.669 Hot water reheating sensor TS4 short-circuited
F.67 Ionisation current out of range
F.670 Buffer tank sensor TS3 open circuit
F.671 Buffer tank sensor TS3 short-circuited
F.672 Thermostat function sensor TS3 open circuit
F.673 Thermostat function sensor TS3 short-circuited
F.68 Flame signal already present at start
F.682 Air mass flow sensor not detected
F.683 Air mass flow sensor faulty
F.684 Non-return flap faulty
F.688 Communication fault with the MZIO module
F.69 Ionisation current out of range (fault logged)
F.693 Flue gas safety limiter open circuit
F.694 Flue gas safety limiter: signals disagree
F.696 Flue gas safety limiter short-circuited
F.70 Internal fault in the burner control unit
F.71 Fan speed not reached
F.72 Fan standstill not reached
F.73 Internal communication interrupted
F.74 System water pressure too low
F.75 No water flow in the system
F.762 Not enough water in the system
F.763 Gas pressure too high
F.764 Fault reported by an additional appliance
F.765 No communication with the additional appliance
F.77 Inconsistent data in the burner control unit
F.78 No communication with the control panel
F.797 Circuit 1 pump mechanical fault
F.799 Electrical fault in the heating pump
F.80 Solar collector sensor TS2 short circuit
F.87 System water pressure too high
F.875 Lost link with the lead boiler (cascade)
F.89 Boiler circulation pump blocked
F.91 Communication fault with the DIO module
F.92 Communication fault with the ADIO module
F.93 Communication fault with the M2IO module
F.94 Communication fault with the SDIO solar module
F.980 Too little water flow to start hot water
F.981 Water flow too low while making hot water
F.982 Boiler pump running dry
F0 Internal control fault
F0-FF Fault in a heating BUS device
F1 Flue gas temperature too high
F2 Safety temperature limiter tripped
F3 Flame detected before the burner starts
F30 Temperature sensor short-circuited
F38 Boiler temperature sensor open circuit
F4 The boiler detects no flame
F5 Air pressure switch or flow sensor fault
F50 Hot water or flue gas sensor short-circuited
F51 Hot water outlet sensor short-circuited
F58 Hot water or room sensor fault
F59 Outlet sensor open circuit or low voltage
F6 Flue gas monitor: boiler locked out
F7 Pressure or hot water sensor fault
F8 Gas valve not closing properly
F9 Fan speed too low
FA The fan does not come to a stop
FC Gas valve or flue fault
FE Coding card or circuit board fault
FF Internal controller fault
Fb Flame lost while running
Fd Burner control unit fault
I.137 No control limitation
I.56 External heat request active
I.57 External boiler lock active
I.59 Boiler settings restored
I.93 Burner held off by the central pump
P.1 Service due soon by time interval
P.37 Service due: time or burner hours reached
P.4 Heating water top-up requested
P.8 Service due by burner hours
S.154 Burner not needed: little heat taken up
S.29 Heating in normal operation
S.36 Comfort mode for hot water
S.59 Flue gas sensor test running
S.60 Summer mode active
S.74 Space heating suppressed for now
S.75 Hot water circulation pump running
S.9 Fan pre-purge before heating
S.94 Heating circuit 1: no external request
S.95 Heating circuit 2: no external request
S.96 Heating circuit 3: no external request
b0 Flue gas temperature sensor short-circuited
b1 Control module communication fault
b4 Internal fault in the control electronics
b5 Internal fault in the controller
b6 Control hardware not recognised correctly
b7 Coding plug or burner control unit fault
b8 Flue gas temperature sensor open circuit
b9 Internal fault in the controller
bA Circuit 2 mixing valve: connection lost
bC Circuit 1 remote control: connection lost
bE Vitotrol remote control fault
bF Wrong LON communication module
bb Circuit 3 mixing valve: connection lost
bd Circuit 2 remote control: connection lost
d1 Burner in fault
d3 Communication fault with the fan unit
d4 Fan air flow or safety temperature limiter
d5 Boiler fan blocked
d6 Fault reported on input DE1 (EA1 extension)
d7 Fault reported on input DE2 (EA1 extension)
d8 Fault reported on input DE3 (EA1 extension)
dA Room temperature sensor of circuit 1 short-circuited
dC Room temperature sensor of circuit 3 short-circuited
dE Room temperature sensor of circuit 2 disconnected
dF Room sensor of heating circuit 3 cut off
db Room temperature sensor of circuit 2 short-circuited
dd Room temperature sensor of circuit 1 disconnected
7 Hot water temperature sensor open circuit
8 Hot water temperature sensor short circuit
10 Outdoor temperature sensor short-circuited
11 Solar collector sensor open circuit
12 Solar collector sensor short circuit
13 Outdoor temperature sensor open circuit
14 Outdoor temperature sensor short circuit
15 Lower solar cylinder sensor open circuit
16 Lower solar cylinder sensor short circuit
18 Outdoor temperature sensor circuit broken
19 Configuration or wireless outdoor sensor fault
20 Flow temperature sensor short-circuited
21 Solar sensor or return sensor fault
22 Solar system sensor out of tolerance
23 Solar circuit commissioning incorrect
24 Hot water circulation pump out of service
25 Solar destratification pump out of service
26 Circulation and destratification pumps out of service
27 Solar circuit commissioning incorrect
28 Flow temperature sensor open circuit
29 Sensor open circuit: low-loss header or return
30 Boiler temperature sensor short-circuited
38 Boiler temperature sensor circuit broken
40 Heating circuit 2 flow sensor short-circuited
41 Circuit M2 return sensor short-circuited
44 Heating circuit 3 flow sensor short-circuited
48 Heating circuit 2 flow sensor open circuit
49 Circuit 2 mixing valve kit wrongly set
50 Hot water sensor short-circuited
51 Hot water outlet sensor short-circuited
52 Flow sensor or buffer tank sensor short-circuited
57 Room temperature sensor open circuit
58 Hot water sensor circuit broken
59 Hot water outlet sensor circuit broken
62 Safety limiter tripped or ventilation link disturbed
63 Flue gas limiter tripped or ventilation fault
64 Flame lost during operation
65 No flame when the burner starts
67 Flame signal (ionisation) out of range
68 Flame detected before ignition
69 Flame signal (ionisation) out of range
70 Gas pressure switch prevents burner start
71 Mains supply voltage too low
72 The fan does not stop
73 Internal extension H1 prevents burner start
74 Temperature limiter short to earth
75 Internal extension H1/H2 short to earth
76 Gas pressure switch short to earth
77 Central electronic module memory fault
78 No link between control panel and central module
80 Insufficient gas supply
81 No ignition spark
82 Flame signal missing or too weak
83 Flame signal present before ignition
84 Boiler's internal CO limit exceeded
85 Insufficient gas supply during calibration
87 System water pressure too high
89 Internal pump blocked
90 Short circuit on solar module sensor 7
91 Short circuit on solar module sensor 10
92 Solar collector sensor short circuit
93 Short circuit on a Vitosolic controller sensor
94 Solar hot water sensor short circuit
95 CO alarm: carbon monoxide limit exceeded
96 CO detector faulty
98 Open circuit on solar module sensor 7
99 Open circuit on solar module sensor 10
100 PlusBus voltage fault
102 Communication module fault
103 Internal communication fault in the control unit
104 Fault reported by an external device
142 Limited communication on the CAN bus
161 Memory error in the central electronics
162 Low voltage at the central electronics
163 Check error in the electronics memory
176 Condensate built up in the heat cell
182 Outlet temperature sensor short-circuited
183 Outlet temperature sensor open circuit
184 Flow sensor or safety limiter short-circuited
185 Flow sensor or safety limiter open circuit
299 Fault in the boiler's clock
345 Overheating: the temperature monitor has tripped
346 Ionisation current calibration error
347 Flue gas recirculation detected
348 Gas modulation valve fault
349 Fan air flow not detected correctly
350 Ionisation current outside the valid range
351 Ionisation current outside the valid range
352 Combustion CO limit exceeded
353 Insufficient gas supply, reduced power
354 Gas modulation valve out of tolerance
355 Flame signal present before ignition
357 Insufficient gas supply
359 No ignition spark
361 No or weak flame signal at start-up
364 System error in the electronics
365 Gas valve relay contact welded
366 Gas valve power does not switch off
367 Gas valve power does not switch off
368 Gas pressure switch fault
369 Flame lost just after ignition
370 Fuel or modulation valve does not close
371 Fan speed too low
372 Repeated flame loss during calibration
373 Too little heat taken off during calibration
374 Ionisation calibration: preparation not completed
375 Ionisation calibration not carried out
376 Ionisation current implausible against previous value
377 Ionisation recalibration: conditions not met
378 Flame lost while stabilising or running
379 Flame signal missing or too weak
380 Flame lost after ignition: lockout
381 Flame lost during operation
382 Fault counter: limit exceeded
383 Gas line possibly fouled
384 Gas line possibly fouled
385 Ionisation current signal short circuit
386 Central electronic module faulty
387 Ionisation current shorted to earth
388 Central electronic module faulty
395 Ignition electrode shorted to earth
396 Central electronic module faulty
399 Burner electrode short-circuited to earth
400 Central electronic module faulty
401 Burner electrode short-circuited to earth
402 Central electronic module faulty
403 Burner electrode short-circuited to earth
404 Central electronic module faulty
405 Burner electrode short-circuited to earth
406 Central electronic module faulty
408 Central electronic module faulty
410 Central electronic module faulty
416 Flue gas temperature sensor wrongly positioned
417 Central electronic module faulty
418 Central electronic module faulty
425 Time synchronisation failed
446 Flow sensor and safety limiter disagree
447 Flame signal (ionisation) mismatch
448 Flame signal (ionisation) mismatch
449 Program timing monitoring fault
451 Program timing monitoring fault
452 Program timing monitoring fault
453 Program sequence synchronisation error
454 Wrong parameter set in the central module
455 Program sequence monitoring fault
456 Program sequence monitoring fault
457 Fan sticking or blocked
458 Faulty reset sequence
461 Flue gas flap fault
462 External gas safety valve stops burner start
463 Dirty combustion air or flue gas recirculation
464 Flame signal too low during calibration
467 Insufficient gas supply during calibration
468 Flame signal too high during calibration
471 System pressure sensor fault
474 Program timing monitoring fault
477 Solar temperature difference fault
517 Remote control not communicating (PlusBus)
527 Wrong parameter set in the central module
528 Wrong parameter set in the central module
540 Condensate building up in the heat cell
544 Circuit 2 flow sensor open circuit
545 Circuit 2 flow sensor short-circuited
574 Circuit 1 room sensor not available
575 Circuit 1 room sensor open circuit
576 Circuit 1 room sensor short-circuited
577 Circuit 2 room sensor not available
578 Circuit 2 room sensor open circuit
579 Circuit 1 room sensor short-circuited
682 Air mass flow sensor missing
683 Air mass flow sensor faulty
684 Flue non-return flap faulty
694 Flue gas safety limiter mismatch
738 Open-Therm remote control not configured
766 Flue gas temperature too high
767 Flue gas temperature too high
799 Heating pump reports an electrical fault
979 Thermostat and OpenTherm control both connected
980 Water flow too low before hot water production
981 Water flow too low during hot water production
982 Heating pump running dry