Solar temperature difference fault
Blocking: it retries by itself
The controller finds that the temperature difference between the solar collectors and the hot water cylinder is out of tolerance: air in the solar circuit, a badly placed sensor or a faulty pump can be the cause. The boiler keeps running, but the solar system only works in a limited way and no longer delivers solar heat.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show 477?
Repair visit: 360 € excl. VAT (381.60 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 477
The meaning depends on the boiler: find yours below.
Temperature differential monitoring error solar collector/storage tank, difference outside tolerance
What our technician checks
- The flow in the solar circuit (none or too low) and its setting
- Air and dirt in the solar circuit
- The system pressure
- The operation of the non-return valves
- The circulation pump: operation, rated speed and soiling
- The safety temperature limiter, if fitted
- The connections and plugs of sensors TS1 (cylinder) and TS2 (collector) on the ADIO module (EM-S1)
- The resistance of sensors TS1 (NTC 10 kΩ) and TS2 (NTC 20 kΩ), plug removed